    Hi,

    I connected this to a  2HP 240v pump motor. Measured current with both a clamp on ammeter and the Drok 200579 is about the same at about 8.2 amps. However the wattage shown is only about 500 watts! Las time I checked Volts x Amps = Watts! I am trying to use this to monitor power used, so it needs to read the same KW used as the power company meter.

    Jon DeLee
    Post count: 0

    Also on Amazon it says the KW counter CAN be reset. How? It’s not in the manual.

     

    Drok
    Keymaster
    Post count: 2971

    Hello  Jon DeLee,

    There are three kinds of power: Active power(P), Apparent pow er(S) ,Reactive power(Q)

    Our meter only monitor Active power(P)

    Apparent power: S= U*I

    Active power : P=U*I*cosφ (cosφ is power factor)

    Different load have different power factor,  so active power is not always equal to U*I.

    For example, the cosφ for pure resistive load is near 1, so the Active power can be closed to U*I ;

    The cosφ for inductive load and capacitive load is between 0-1, so the Active pow er is less than U*I.

    Our meter also read power factor. You can check that.

    And the reset button is under the lower right of meter, there is a hole, you can press it with wooden stick or other thing, just hold 5 seconds, then kwh will be reset.